Regional Medical Center Saves $20,000 & Restores HVAC System Performance Through Ultraviolet-C Technology


Kentucky regional medical center transforms HVAC performance; delivers 35 percent
increase in airflow; reduces energy consumption using Ultraviolet-C energy

Seeing is believing. At least that’s often the case with ultraviolet germicidal irradiation, which uses short-wavelength Ultraviolet C (UV-C) light to kill microorganisms and degrade organic matter in HVACR equipment. The technology has been used since the 1990s to eliminate microbial and organic materials buildup on cooling coils, air filters, duct surfaces and drain pans. A UV-C equipped system yields cleaner air, uses less energy and needs less maintenance. In fact, UV-C energy can slash 10 to 25 percent of HVAC energy use. And the cost is less than a fraction of a coil replacement.

But, despite this proven track record, some facility engineers remain uncertain. They are quickly won over, however, once they see hard data proving the technology’s effectiveness.

That’s what happened at a 359-bed facility in Kentucky. Engineers there struggled to keep the hospital’s cafeteria cool amid the Blue Grass State’s humid climate. Condensate in the air handling unit (AHU) serving the food service area was leaving a residue in the coil, a buildup that reduced airflow through the unit from the 14,000 CFM design parameter to around 10,000 CFM – nearly 30 percent less than what was originally specified. That, of course, meant the unit couldn’t provide enough cooling volume.

“The air handler wasn’t able to help keep the café and kitchen cool during peak demand, especially during standard meal times in July and August, when occupancy and thermal loads were at their highest,” recalls the hospital’s Director of Engineering.

In an attempt to boost cooling capacity, the hospital’s maintenance staff tried to increase the volume of airflow over the coil by performing up to three mechanical coil cleanings per year at roughly $300 per treatment. According to the engineer, the cafeteria AHU was the worst performer among the medical center’s roughly 30 air handlers, and he was considering replacing it – a task that would cost more than $20,000 and require the unit to be shut down for two to three days.

It was decided to put that plan on hold after speaking with Sales Engineer Charles Haskins with Thermal Equipment Sales.

While at a meeting of the Kentucky Society of Healthcare Engineers, Haskins made the hospital’s Director of Engineering an offer he couldn’t refuse; allow for the installation of UV-C lamps in the cafeteria air handler and if performance didn’t improve in six weeks, the hospital wouldn’t pay a penny.

“Having not tried this technology, we had some skepticism regarding the UV-C energy’s ability to improve airflow and heat-exchange efficiency,” the Director admits. “It’s hard to justify capital investments for equipment that is 20 years old and was earmarked for replacement.”

In an attempt to win approval, Haskins arranged for a UV-C technology primer from UV Resources (UVR), a leading manufacturer of UV-C equipment. According to UVR, skepticism is a common reaction among facility engineers who are unfamiliar with the benefits of UV-C.

“Although UV-C has been used extensively in heathcare and institutional applications successfully for more than three decades, many facility managers remain skeptical,” UVR vice president Dean Saputa, says. “As air-conditioning equipment ages, its ability to maintain adequate space temperatures and humidity levels decline. Most often, the culprit is reduced coil heat-transfer effectiveness, or the ability of an AHU’s cooling coils to remove heat from the air. UV-C systems remove organic growth on the outer and inner surfaces of the coil, thereby restoring the coil’s heat transfer efficiency to ‘as-built’ specifications.”

Saputa and Haskins were certain that they could restore the cafeteria’s airflow levels and meet the desired temperature set point, simply by installing the UV Resources RLM Xtreme™ system.

In the end, an independent project audit vindicated the duo’s daring claim by documenting a 35 percent increase in airflow, or an additional 3,700 CFM, as well as the ability to achieve the hospital’s cooling set points in the cafeteria.

How it Works

The RLM Xtreme is a highoutput fixtureless system that offers the flexibility to be easily configured into most any HVAC plenum. The configuration installed in the hospital cafeteria’s AHU consisted of four T5 (5/8-inch diameter), 61-inch long UV-C lamps, a unique LampHolder that allows the lamp to be affixed in any position inside the air handler, and a power supply with a powdercoated, heavy-gauge galvanized steel and NEMA-2 rated housing. Its EncapsuLamp™ (FEP lamp coating) technology protects the system and airstream from glass and mercury residues should an accidental lamp break occur.

The UV lamps were installed on the downstream, air-exiting side of the coil, where they are most productive killing mold and bacteria and degrading all other organic materials. The UV-C wavelength removes this organic growth rather quickly, often in less than one month – a process that doesn’t produce any residual matter. The destroyed organic material is removed through normal condensate production until the coil is completely clean.

A properly sized and installed set of lamps will noticeably clean a coil in about 30 days with continued improvements up to one year later on severely clogged coils. The UV-C fixtures can be installed in about two hours at an installed cost (materials and labor) of roughly $0.15 or less per CFM of airflow capacity. For the Kentucky Medical Center, the UV-C installation represented about 10 percent of the cost of a new, replacement coil.

Show Me the Numbers

Installation of the RLM Xtreme fixtures was completed in September 2014. The hospital cafeteria’s AHU was cleaned a few weeks before the installation, but continued to perform poorly.

“Outside temperatures were about 90 degrees,” recalls Haskins before the UV-C lamps were installed. “The AHU was unable to meet the food center’s thermostat set points. The fan was running as fast as it could, but the unit couldn’t get temperatures below 84 degrees in the kitchen or 78 degrees in the café.”

Once the UV-C fixtures were installed, the team planned to evaluate progress following a three-month trial. To document progress, the cafeteria AHU was connected to a Super Scientifics manometer to measure pressure drop across the coil, and an Ebtron air monitoring station to record airflow levels. Both devices were equipped with data loggers.

The data was analyzed in mid-December. By that time, the baseline measured airflow in September of 10,300 CFM had risen 35 percent to 14,192 CFM, which enabled the AHU to now maintain the desired set point temperature. The initial measured pressure drop across the coil of 2.66 inches WG decreased to .69 inch WG, which meant that the fan amperage was obviously lower while achieving and maintaining desired temperature. “The higher pressure drop across a dirty coil means the fan would have to work harder to compensate for the higher pressure drop and the coil’s diminished cooling capacity,” says Saputa, who notes that the increase in airflow volume and pressure drop reduction are not related According to the facility, the team plans their first retrofits for the air handlers serving the operating rooms, patient rooms, and radiology department – a total of four additional units.

Other area hospitals are also now showing interest in the proven technology.

“Officials at other medical centers in the area learned about the turnaround performance and are now exploring similar upgrades,” concludes Saputa. “Good news travels fast.”


Product Details: RLM Xtreme™

The UV Resources RLM Xtreme fixtureless UV-C lamp system delivers high-output ultraviolet energy to irradiate coils and eliminate mold, bacteria and microbes in demanding, high-volume HVAC systems.

High-output RLM Xtreme lamps are single-ended, which facilitates a simple, but sturdy, mounting system and selection of s single size lamp for all fixtures. This reduces the number of spares needed on hand, and enables quantity-purchasing discounts during annual replacements.

Ideal for both new and retrofit applications, Xtreme lamps eliminate the need for rows of costly, cumbersome and potentially unsafe metal and glass fixturing.

The concept of the Xtreme lamp system was fueled by a growing demand for a UV-C system that provides application versatility, ease of sizing and installation, and affordability. Whether your application is coil irradiation, killing pathogenic microorganisms or extending HVAC system life, Xtreme’s high-output performance combines the best UV-C components in a simple and flexible system that features the industry’s lowest cost of ownership — making it the best value on the market.

After a mere 90 days, airflow is back to design specs and we are able to maintain the desired temperature set points in the kitchen and cafeteria,” he says. “The AHU motor is drawing less amps, saving the hospital energy.